Self-contained systems
These systems have a power cell within each light fitting and often have a red LED light to show that they are receiving a charge when power is on.
Inspection: by owner every month, and by IQP every year.
Requirements:
- Required monthly, or 6-monthly if system is less than 10 years old.
-
Check operation of all fittings by using Test facility or circuit breaker marked “Emergency lighting” or similar.
-
Ensure all lights clean and clear from obstruction and remain lit for a minimum of 15 minutes.
RETURN SYSTEM TO STANDBY MODE IF NOT ON A TIMER